    No headers

    The following tables provide details about the assumptions used during conceptual energy analysis for each building type. These assumptions are based on ASHRAE standards.

    Automotive facility

    ParameterValue
    Occupancy ScheduleWarehouse
    People/100 sq. M.15
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)9.7
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)NULL
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)27.4
    Unoccupied Cooling Set Point (C)29.4

    Convention center

    ParameterValue
    Occupancy ScheduleAssembly
    People/100 sq. M.25
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)12.9
    Equipment Load Density (W/sq. M.)10.3
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)3.1
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Courthouse

    ParameterValue
    Occupancy ScheduleOffice
    People/100 sq. M.3.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)12.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)2.9
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Dining bar lounge or leisure

    ParameterValue
    Occupancy ScheduleRestaurant
    People/100 sq. M.35
    People Sensible Heat Gain (W/person)81
    People Latent Heat Gain (W/person)81
    Lighting Load Density (W/sq. M.)14.0
    Equipment Load Density (W/sq. M.)8.5
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)4.7
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Dining cafeteria fast food

    ParameterValue
    Occupancy ScheduleRestaurant
    People/100 sq. M.50
    People Sensible Heat Gain (W/person)81
    People Latent Heat Gain (W/person)81
    Lighting Load Density (W/sq. M.)15.1
    Equipment Load Density (W/sq. M.)8.5
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)4.7
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Dining family

    ParameterValue
    Occupancy ScheduleRestaurant
    People/100 sq. M.35
    People Sensible Heat Gain (W/person)81
    People Latent Heat Gain (W/person)81
    Lighting Load Density (W/sq. M.)17.2
    Equipment Load Density (W/sq. M.)8.5
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)5.1
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Dormitory

    ParameterValue
    Occupancy ScheduleResidential
    People/100 sq. M.10
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)4
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Exercise center

    ParameterValue
    Occupancy ScheduleRetail
    People/100 sq. M.10
    People Sensible Heat Gain (W/person)110
    People Latent Heat Gain (W/person)183
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)10.8
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Fire station

    ParameterValue
    Occupancy ScheduleResidential
    People/100 sq. M.3.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)8.5
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Gymnasium

    ParameterValue
    Occupancy ScheduleRetail
    People/100 sq. M.33.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.8
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)13
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Hospital or healthcare

    ParameterValue
    Occupancy ScheduleHealth
    People/100 sq. M.10
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)12.9
    Equipment Load Density (W/sq. M.)12.7
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)13
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Hotel

    ParameterValue
    Occupancy ScheduleHotel/Motel
    People/100 sq. M.2.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)5.4
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)5.5
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Library

    ParameterValue
    Occupancy ScheduleOffice
    People/100 sq. M.10
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)14.0
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)8.5
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Manufacturing

    ParameterValue
    Occupancy ScheduleWarehouse
    People/100 sq. M.2.5
    People Sensible Heat Gain (W/person)110
    People Latent Heat Gain (W/person)183
    Lighting Load Density (W/sq. M.)14.0
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)8
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Motel

    ParameterValue
    Occupancy ScheduleHotel/Motel
    People/100 sq. M.2.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)5.4
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)5.5
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Motion picture theatre

    ParameterValue
    Occupancy ScheduleAssembly
    People/100 sq. M.75
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)12.9
    Equipment Load Density (W/sq. M.)5.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)2.7
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Multi family

    ParameterValue
    Occupancy ScheduleResidential
    People/100 sq. M.2.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)7.5
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)NULL
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)1.1
    Unoccupied Cooling Set Point (C)29.4

    Museum

    ParameterValue
    Occupancy ScheduleRetail
    People/100 sq. M.33.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)11.8
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)4.6
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Office

    ParameterValue
    Occupancy ScheduleOffice
    People/100 sq. M.3.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)14.4
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)8.5
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Parking garage

    ParameterValue
    Occupancy ScheduleWarehouse
    People/100 sq. M.2.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)3.2
    Equipment Load Density (W/sq. M.)3.2
    Infiltration Flow (ACH)5
    Outside Air (ventilation air) Flow Per Person (liters per second)NULL
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)27.4
    Unoccupied Cooling Set Point (C)29.4

    Penitentiary

    ParameterValue
    Occupancy ScheduleResidential
    People/100 sq. M.10
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)4.9
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Performing arts theatre

    ParameterValue
    Occupancy ScheduleAssembly
    People/100 sq. M.75
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)17.2
    Equipment Load Density (W/sq. M.)5.8
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)4.9
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Police station

    ParameterValue
    Occupancy ScheduleOffice
    People/100 sq. M.3.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)5.4
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Post office

    ParameterValue
    Occupancy ScheduleOffice
    People/100 sq. M.3.5
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)11.8
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)4.9
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Religious building

    ParameterValue
    Occupancy ScheduleAssembly
    People/100 sq. M.75
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)14.0
    Equipment Load Density (W/sq. M.)10.3
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)8.5
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Retail

    ParameterValue
    Occupancy ScheduleRetail
    People/100 sq. M.10
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)16.1
    Equipment Load Density (W/sq. M.)10.1
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)2.8
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    School or university

    ParameterValue
    Occupancy ScheduleSchool
    People/100 sq. M.25
    People Sensible Heat Gain (W/person)73
    People Latent Heat Gain (W/person)59
    Lighting Load Density (W/sq. M.)12.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.25
    Outside Air (ventilation air) Flow Per Person (liters per second)7.8
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Single family

    ParameterValue
    Occupancy ScheduleResidential
    People/100 sq. M.0.945
    People Sensible Heat Gain (W/person)72
    People Latent Heat Gain (W/person)45
    Lighting Load Density (W/sq. M.)4.8
    Equipment Load Density (W/sq. M.)4.6
    Infiltration Flow (ACH)0.5
    Outside Air (ventilation air) Flow Per Person (liters per second)NULL
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)1.1
    Unoccupied Cooling Set Point (C)29.4

    Sports arena

    ParameterValue
    Occupancy ScheduleAssembly
    People/100 sq. M.75
    People Sensible Heat Gain (W/person)73.3
    People Latent Heat Gain (W/person)58.6
    Lighting Load Density (W/sq. M.)11.8
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)6.7
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Town hall

    ParameterValue
    Occupancy ScheduleOffice
    People/100 sq. M.33.5
    People Sensible Heat Gain (W/person)73.3
    People Latent Heat Gain (W/person)58.6
    Lighting Load Density (W/sq. M.)11.8
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)4
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Transportation

    ParameterValue
    Occupancy ScheduleAssembly
    People/100 sq. M.50
    People Sensible Heat Gain (W/person)73.3
    People Latent Heat Gain (W/person)58.6
    Lighting Load Density (W/sq. M.)10.9
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)3.1
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Warehouse

    ParameterValue
    Occupancy ScheduleWarehouse
    People/100 sq. M.1.5
    People Sensible Heat Gain (W/person)73.3
    People Latent Heat Gain (W/person)58.6
    Lighting Load Density (W/sq. M.)8.6
    Equipment Load Density (W/sq. M.)4.6
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)4.1
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)3.7
    Unoccupied Cooling Set Point (C)29.4

    Workshop

    ParameterValue
    Occupancy ScheduleWarehouse
    People/100 sq. M.5
    People Sensible Heat Gain (W/person)81
    People Latent Heat Gain (W/person)139
    Lighting Load Density (W/sq. M.)15.1
    Equipment Load Density (W/sq. M.)10.8
    Infiltration Flow (ACH)0.1
    Outside Air (ventilation air) Flow Per Person (liters per second)NULL
    Outside Air (ventilation air) Flow Per Area (cubic meters per hour per square meter)1.1
    Unoccupied Cooling Set Point (C)29.4