Space Type Data

    Table of contents
    No headers

    The following tables list the default settings for space types in Vasari.

    Active Storage

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Warehouse 7 am - 4 pm
    People/100 sq. M. 3.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.8
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Active Storage - Hospital/healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 3.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Air/Train/Bus - Baggage Area

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 100.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Airport Concourse

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 100
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.6
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Atrium - Each additional floor

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 33.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.2
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Atrium - First 3 floors

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 33.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.6
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Audience/Seating Area - Penitentiary

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.7
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Audience/Seating Area - Exercise Center

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Audience/Seating Area - Gymnasium

    Parameter Default Value
    Occupancy Schedule Common Commercial 7 am - 6 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.4
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Audience/Seating Area - Sports Arena

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.4
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Audience/Seating Area - Convention Center

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.7
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Audience/Seating Area - Motion Picture Theatre

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Audience/Seating Area - Performing Arts Theatre

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 2.6
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Audience/Seating Area - Religious

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 120
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 1.7
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Audience/Seating Area - Police/Fire Station

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 50.0
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.93
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Audience/Seating Area - Courthouse

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.93
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Audience/Seating Area - Auditorium

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.93
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Bank Customer Area

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 1.49
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Banking Activity Area - Office

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.5
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.3
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Barber and Beauty Parlor

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 25.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1
    Power Load Density (W/sq. ft.) 2
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Card File and Cataloguing - Library

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Classroom/Lecture/Training - Penitentiary

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 65.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Classroom/Lecture/Training

    Parameter Default Value
    Occupancy Schedule School 8 am - 9 pm
    Power Schedule School 7 am - 9 pm
    People/100 sq. M. 65.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.4
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Confinement Cells - Penitentiary

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 25.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.93
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Confinement Cells - Court House

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 25.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Conference/Meeting/Multipurpose

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 50.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Corridor/Transition

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.5
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Corridor/Transition - Manufacturing Facility

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 00.5
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Corridor w/Patient Waiting Exam - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Court Sports Area - Sports Area

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.3
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Courtroom - Court House

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.3
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Department Store Sales - Retail

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 15.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.14
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Detailed - Manufacturing Facility

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.1
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dining Area

    Parameter Default Value
    Occupancy Schedule Restaurant Lunch and Dinner
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Dining Area - Hotel

    Parameter Default Value
    Occupancy Schedule Restaurant Lunch and Dinner
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Dining Area - Family Dining

    Parameter Default Value
    Occupancy Schedule Restaurant Lunch and Dinner
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 2.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Dining Area - Lounge/Leisure Dining

    Parameter Default Value
    Occupancy Schedule Restaurant Lunch and Dinner
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 1.4
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dining Area - Motel

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dining Area - Transportation

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 100.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 0.93
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dining Area - Penitentiary

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 100.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dining Area - Civil Services

    Parameter Default Value
    Occupancy Schedule Restaurant Lunch and Dinner
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 100.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 275
    Lighting Load Density (W/sq. ft.) 0.93
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dormitory Bedroom

    Parameter Default Value
    Occupancy Schedule Home 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 155
    Lighting Load Density (W/sq. ft.) 1.11
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Dormitory Study Hall

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 155
    Lighting Load Density (W/sq. ft.) 1.11
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Dressing/Locker/Fitting Room - Gymnasium

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.6
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dressing/Locker/Fitting Room - Court House

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Lighting Schedule Office Lighting 6 am - 11 pm
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.56
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dressing/Locker/Fitting Room - Performing Arts Theatre

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.56
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dressing/Locker/Fitting Room - Auditorium

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.56
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Dressing/Locker/Fitting Room - Exercise Center

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.56
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Electrical/Mechanical

    Parameter Default Value
    Occupancy Schedule Restaurant Lunch and Dinner
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 3.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.5
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Elevator Lobbies

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.2
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Emergency - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.7
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Equipment Room - Manufacturing Facility

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 3.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Exam/Treatment - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.5
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Exercise Area - Exercise Center

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 710
    People Latent Heat Gain (Btu/hr) 1090
    Lighting Load Density (W/sq. ft.) 0.93
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Exercise Area - Gymnasium

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 710
    People Latent Heat Gain (Btu/hr) 1090
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Exhibit Space - Convention Center

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 50.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Fellowship Hall - Religious Buildings

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 120.0
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Fine Material - Warehouse

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Warehouse 7 am - 4 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.4
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Fine Merchandise - Sales Area Retail

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 15.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.14
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Fire Station Engine Room - Police Fire Station

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.8
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Food Preparation

    Parameter Default Value
    Occupancy Schedule Restaurant Lunch and Dinner
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Garage Service/Repair - Automotive Facility

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.7
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    General High Bay - Manufacturing Facility

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.7
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    General Low Bay - Manufacturing Facility

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    General Exhibition - Museum

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 40.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Hospital - Nursery - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.6
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Hospital - Medical Supplies - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 3.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.4
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Hospital/Radiology- Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.4
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Hotel/Conference Center - Conference/Meeting

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 50.0
    People Sensible Heat Gain (Btu/hr) 225
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Inactive Storage

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Warehouse 7 am - 4 pm
    People/100 sq. M. 3.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.3
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Judges Chambers - Court House

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 50.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Laboratory - Office

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.4
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Laundry - Ironing and Sorting

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 475
    Lighting Load Density (W/sq. ft.) 0.56
    Power Load Density (W/sq. ft.) 3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Laundry - Washing - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 275
    People Latent Heat Gain (Btu/hr) 475
    Lighting Load Density (W/sq. ft.) 0.6
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Library - Audio Visual - Library - Audio Visual

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 25.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Living Quarters - Dormitory

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Residential Lighting All Day
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 155
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Living Quarters - Motel

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 155
    Lighting Load Density (W/sq. ft.) 1.11
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Living Quarters - Hotel

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 155
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Lobby

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 155
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Lobby - Religious Building

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Lobby - Motion Picture Theatre

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Lobby - Auditorium

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Lobby - Performing Arts Theatre

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 3.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Lobby - Post Office

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.3
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Lobby - Hotel

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Lounge or Recreation

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.21
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Mail Concourse Sales Area - Retail

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 40.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.7
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Mass Merchandising Sales Area - Retail

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Warehouse 7 am - 4 pm
    People/100 sq. M. 15.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.11
    Power Load Density (W/sq. ft.) 0.1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Medium/Bulky Material - Warehouse

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Warehouse 7 am - 4 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Merchandising Sales Area - Retail

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 15.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.14
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Museum and Gallery - Storage

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.84
    Power Load Density (W/sq. ft.) 0.2
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Nurse Station - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.3
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Office - Enclosed

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.3
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Office - Open Plan

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.3
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Office - Common Activity Areas - Inactive Storage

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Warehouse 7 am - 4 pm
    People/100 sq. M. 3.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.28
    Power Load Density (W/sq. ft.) 0.2
    Electrical Equipment Radiant Percentage 0.3
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Operating Room - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.2
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Other Televised Playing Area - Sports Arena

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 150.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.4
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Parking Area - Attendant Only - Parking Garage

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.19
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Parking Area - Pedestrian - Parking Garage

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.2
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Patient Room - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.7
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Personal Services Sales Area - Retail

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 15.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.14
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Pharmacy - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Physical Therapy - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Playing Area Gymnasium

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 710
    People Latent Heat Gain (Btu/hr) 1090
    Lighting Load Density (W/sq. ft.) 1.4
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Plenum

    Parameter Default Value
    Occupancy Schedule Cooling/Heating Off 24 hrs
    Power Schedule Cooling/Heating Off 24 hrs
    People/100 sq. M. 00
    People Sensible Heat Gain (Btu/hr) 0
    People Latent Heat Gain (Btu/hr) 0
    Lighting Load Density (W/sq. ft.) 0
    Power Load Density (W/sq. ft.) 0
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0
    Carpet (Y/N) N

    Police Station Laboratory - Police/Fire Stations

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 25.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.39
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Public and Staff Lounge - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 25.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.84
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Reading Area - Library

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Reception/Waiting - Transportation

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 100.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Reception/Waiting - Motel

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Reception/Waiting - Hotel

    Parameter Default Value
    Occupancy Schedule Hotel 24 hrs
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 30.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.1
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Recovery - Hospital/Healthcare

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.8
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Restoration - Museum

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 40.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.7
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Restrooms

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.9
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Ring Sports Area - Sports Arena

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 70.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.7
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Sleeping Quarters - Police/Fire Station

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 105
    Lighting Load Density (W/sq. ft.) 0.3
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Sorting Area - Post Office

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 5.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.2
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Specialty Store Sales Area - Retail

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 15.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.14
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Stacks - Library

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.7
    Power Load Density (W/sq. ft.) 1.5
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Stairs - Inactive

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.56
    Power Load Density (W/sq. ft.) 0.2
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Stairway

    Parameter Default Value
    Occupancy Schedule Common Office 8 am - 5 pm
    Power Schedule Office Lighting 6 am - 11 pm
    People/100 sq. M. 10.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 0.6
    Power Load Density (W/sq. ft.) 0.3
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Supermarket Sales Area - Retail

    Parameter Default Value
    Occupancy Schedule Retail Facility 7 am - 8 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 8.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.1
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Terminal - Ticket Counter - Transportation

    Parameter Default Value
    Occupancy Schedule Healthcare Facility 8 am - 9 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 100.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.5
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y

    Workshop - Workshop

    Parameter Default Value
    Occupancy Schedule Warehouse 7 am - 4 pm
    Power Schedule Warehouse 7 am - 4 pm
    People/100 sq. M. 20.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 1.9
    Power Load Density (W/sq. ft.) 1
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) N

    Worship - Pulpit Choir - Religious

    Parameter Default Value
    Occupancy Schedule Large Assembly Hall 8 am - 10 pm
    Power Schedule Retail Lighting 7 am - 8 pm
    People/100 sq. M. 120.0
    People Sensible Heat Gain (Btu/hr) 250
    People Latent Heat Gain (Btu/hr) 200
    Lighting Load Density (W/sq. ft.) 2.4
    Power Load Density (W/sq. ft.) 0.54
    Electrical Equipment Radiant Percentage 0.5
    Infiltration Flow (CFM/sq. ft.) 0.038
    Carpet (Y/N) Y